|
MECHANICS - CASE STUDY SOLUTION
|
![](../ebook/mechanics/ch09/sec092/media/d9231.gif)
Building Load
|
|
This case requires the center column for a basic building be designed to carry
the roof load. The roof load has a dead
and live roof load of, 300 and 250 kg/m2, respectively. Generally,
a dead load is the static, non-changing load such as roof weight and equipment
on the roof. On the other hand, a live load is changing loads, such as snow
or wind. The total (worst case) should be considered when designing the column.
The other major condition is that the selection of the center column needs
to be specified from a group of I-beams that are in storage. The best column
will be the lightest column that can withstand the roof load. Both buckling and
compression failure should be checked.
|
|
|
|
|
Center Column Load
|
![](../ebook/mechanics/ch09/sec092/media/d9232.gif)
Roof Load Area
Carried by Center Column
|
|
The center column will need to carry the roof load that is half way to each
of the other columns. The total roof area carried by the center column is 10
m by 8 m as shown in the diagram at the left. The total roof load over this area
is
F = (10 m)(8 m)(300 + 250 kg/m2)(9.81
m/s2)
= 431.6 kN
The last term is the standard gravitational constant.
The column requires a factor of safety of 2.5, so the design load needs to be
increased by a factor of 2.5, giving
Pcr = 2.5 (431.6 kN) = 1.079 MN
|
|
|
|
|
|
Required Moment of Inertia
|
![](../ebook/mechanics/ch09/sec092/media/d9233.gif)
Center Column Load
![](../ebook/mechanics/ch09/sec092/media/d9234.gif)
Both Directions must be
Considered for Buckling
|
|
The minimum moment of inertia is needed so that a suitable wide-flange I-beam
can be chosen. Since both ends are assumed to be fixed, the Euler buckling equation
is
![](../ebook/mechanics/ch09/sec092/media/eq9231.gif)
Substituting known values give,
![](../ebook/mechanics/ch09/sec092/media/eq9232.gif)
Solving for the moment of inertia,
I = 6.696 × 10-6 m4 =
6.696 × 106 mm4
The I-beam must have this moment of inertia (or greater) in both direction.
Generally, I-beams have a higher inertia around the x-axis, but buckling can
occur about either axis.
|
|
|
|
|
|
Column Selection
|
|
|
There are currently 18 different wide-flange I-beams available for the construction
of the building. They are list below.
|
|
|
|
Section
Number |
Weight |
Area
mm2 |
Ix
106 mm4 |
Iy
106 mm4 |
W310 x 67 |
67 |
8,530 |
145 |
20.7 |
x 39 |
39 |
4,930 |
84.8 |
7.23 |
x 33 |
33 |
4,180 |
65.0 |
1.92 |
x 24 |
24 |
3,040 |
42.8 |
1.16 |
x 21 |
21 |
2,680 |
37.0 |
0.986 |
W250 x 58 |
58 |
7,400 |
87.3 |
18.8 |
x 45 |
45 |
5,700 |
71.1 |
7.03 |
x 28 |
28 |
3,620 |
39.9 |
1.78 |
x 22 |
22 |
2,850 |
28.8 |
1.22 |
x 18 |
18 |
2,280 |
22.5 |
0.919 |
W200 x 59 |
59 |
7,580 |
61.2 |
20.4 |
x 46 |
46 |
5,890 |
45.5 |
15.3 |
x 36 |
36 |
4,570 |
34.4 |
7.64 |
x 22 |
22 |
2,860 |
20.0 |
1.42 |
W150 x 37 |
37 |
4,730 |
22.2 |
7.07 |
x 30 |
30 |
3,790 |
17.1 |
5.54 |
x 22 |
22 |
2,860 |
12.1 |
3.87 |
x 24 |
24 |
3,060 |
13.4 |
1.83 |
Wide-Flange Beams Available |
|
|
|
|
|
Both Ix and Iy must be at least 6.696 × 106 mm4 to
satisfy the buckling requirements. The critical moment of inertia is Iy.
There are several beams that have moment of inertia's greater than 6.696 in both
directions. However, the lightest one is
W200 x 36
|
|
|
|
|
|
Compression Stress Check
|
|
|
Even though the column was designed assuming buckling, the compression
stress should be checked to make sure it does not exceed the yield stress of
the material. The compression stress is
σ = P/A = (1.079 MN)/(4,570 mm2)
= 236.1 MPa
This is less than the yield stress of 250 MPa for structural steel and will
not yield in compression.
|
|
|
|
|